SPCSPC

SPC Pump Control Panel

The SPC pump control panel provides the interface between the pump motor starter and the Singer pump control valve. The SPC ensures that the pump starts and stops without causing line surges.

The SPC panel energizes the control valve pilot solenoid simultaneously with pump start. When pump shut-down is required the panel keeps the pump running while the pilot solenoid is de-energized. The panel turns the pump off just as the control valve completes its full stroke travel. The SPC panel is equipped with delay timers and emergency fault contacts to provide the customer with local and remote indication for various operational failure conditions. The SPC panel is connected to the pilot solenoid and limit switch that are standard components in the control valve pilot system. The panel is also connected to the customer supplied pump discharge pressure switch and the pump motor starter. A second limit switch and emergency shutdown solenoid are optional components for the control valve pilot system. The logical arrangement of indicator lights with the Hand Off Automatic (HOA) selector switch provides easy supervision of the sequencing and the operating status. The logical arrangement of Hand/Automatic selector, start, stop and emergency stop switches make the operating simple and easy to execute.

  • Automatically interfaces pump and control valve to avoid starting and stopping surges
  • Visual indication of operational status
  • Simple to install
  • Suitable for use with either in-line booster or deep well by-pass pump control valves